Eaton XTJL Jockey Lite Pump Controller

This controller is quoted to your specifications. Call or Request a Quote Today.

The Eaton XTJL is Eaton's JOCKEY Lite jockey pump controller, a simple, pressure-switch-based across-the-line controller for keeping fire protection system pressure up. Instead of a touchscreen, it uses a mechanical dual-setting pressure switch and a Hand-Off-Auto selector switch, making it a straightforward, economical choice for jockey pump control. Every XTJL is built to order, so we quote each one to your motor, voltage, enclosure and options. Call (786) 336-5783 or send us your catalog number.

How the XTJL works

The XTJL operates across-the-line: full voltage is applied to the motor for starting through a single motor starter, with starting inrush current of approximately 600% of the motor's rated full load amperes. A dual-setting 15–290 PSI pressure switch senses a drop in system pressure and actuates the jockey pump contactor. Adjustment screws set the pressure range and differential, and the switch provides one set of form-C output contacts rated at 10A. The controller can be run in Auto or Hand from the selector switch.

If you need programmable timers, alarms, history and a touchscreen, see the XTJP JOCKEY Touch controller, or the XTJY for wye-delta starting.

JOCKEY Lite features

  • Dual-setting pressure switch: 15–290 PSI range with adjustable range and differential; a 90–450 PSI ALCO pressure switch is available as an option (P3)
  • Hand-Off-Auto selector switch for automatic or manual operation
  • Combination motor controllers: Eaton combination motor controllers combine the circuit breaker and overload in one device
  • Sealed rotary handle: can be padlocked in the OFF position, and the door can't be opened with the handle in the ON position
  • 120V control power transformer wired as standard on all JOCKEY Lite controllers
  • XT power controls: Eaton XT components with global ratings, compact size and a modular, plug-in design
  • Enclosures: NEMA 2 standard; NEMA 3R, 3, 4, 4X and 12 available
  • Standards: meets NFPA 20 and CE mark requirements, meets or exceeds UL 508, and is CSA approved

Ratings

Line voltage Motor horsepower
200–208V, three phase 1/3 – 20 HP
220–240V, three phase 1/3 – 20 HP
380–415V, three phase 1/3 – 40 HP
440–480V, three phase 1/3 – 50 HP
550–600V, three phase 1/3 – 50 HP
120V, single phase 1/3 – 2 HP
240V, single phase 1/3 – 5 HP

XTJL catalog numbers explained

XTJL catalog numbers use horsepower and a voltage letter. For example, XTJL-5-A-L1 is a 5 HP, 208V/60Hz three phase JOCKEY Lite controller with English labels in the standard NEMA 2 enclosure.

Segment Example Meaning
Model XTJL JOCKEY Lite jockey pump controller
Horsepower 5 1/3, 1/2, 3/4, 1, 1.5, 2, 3, 4, 5, 7.5, 10, 15, 20, 25, 30, 40 or 50 HP. Higher horsepowers aren't available on all models.
Voltage A Three phase: A 208V/60Hz · B 240V/60Hz · C 380V/50Hz · D 480V/60Hz · E 600V/60Hz · F 415V/50Hz · H 380V/60Hz · J 400V/50Hz · K 400V/60Hz
Single phase: G1 120V/60Hz · G2 240V/60Hz · G3 208V/60Hz
Language L1 L1 English · L2 French · L5 Spanish · L6 Portuguese · L11 Turkish
Options (none) Added codes for enclosures and accessories (see below)

Note: on the XTJL, G1, G2 and G3 are single phase voltage codes. They aren't the amperage ranges used in XTJP and XTJY part numbers.

XTJL options

C1 / C2 Extra contacts: pump run / AC power failure
E1 / E2 / E3 NEMA 3R / NEMA 4 / NEMA 12 enclosure
E5 / E9 / E10 NEMA 4X: 304 stainless / painted steel / 316 stainless
E8 / EX Tropicalization / export crating
POL / PRL "Power On" light / "Pump Run" light
P3 ALCO 90–450 PSI pressure switch
P7 / P8 Low suction pressure switch / low suction shutdown (requires P7)
R1 / R2 / R3 Space heater / with thermostat / with humidistat
S / T / Z Sequential start timer / run period timer / elapsed time meter

What we need for a quote

  • Jockey pump motor horsepower
  • Supply voltage, phase and frequency
  • System pressure range, if above 290 PSI (P3 option)
  • Enclosure type
  • Options and label language

Have a full catalog number, a spec section or a photo of an existing nameplate? Send that instead and we'll match it. Call (786) 336-5783 or request a quote.

Bid submittals and documents

Three phase

Single phase

Replacement parts

Need parts for an existing jockey pump controller? Shop XTJP/XTJY components or browse all Eaton fire pump controller replacement parts.

Installation, wiring and commissioning should follow Eaton's instruction manual and NFPA 20 and be performed by qualified personnel.