Eaton XTJP Jockey Pump Controller (JOCKEY Touch)
This controller is quoted to your specifications. Call or Request a Quote Today.
The Eaton XTJP is Eaton's JOCKEY Touch across-the-line jockey pump controller. It keeps fire protection system pressure up by running the jockey pump, and it uses a microprocessor-based color touchscreen to monitor and program every function and value. Standard configurations are available to order online below; other configurations are built to order and quoted to your motor, voltage, enclosure and options. Call (786) 336-5783 or send us your part number.
How the XTJP works
The XTJP operates across-the-line: full voltage is applied to the motor for starting through a single motor starter, with starting inrush current of approximately 600% of the motor's rated full load amperes. Pressure input comes from a 4-20mA pressure sensor, and start and stop points are adjustable in 1 PSI (or 0.1 BAR) increments. For jockey pump motors that need reduced-voltage starting, see the XTJY wye-delta jockey pump controller. For a simpler pressure-switch-based controller, see the XTJL Jockey Lite.
JOCKEY Touch features
- Color touchscreen: door-mounted, type 4/4X rated display showing supply voltage on all phases, current pressure, start pressure and stop pressure, with programming possible with the door closed
- Combination motor controllers: Eaton combination motor controllers combine the circuit breaker and overload in one device
- Sealed rotary handle: can be padlocked in the OFF position, and is interlocked so the door can't be opened with the handle ON except by a tool-operated defeater
- Universal supply voltage: auto-detects three phase supply from 200–600VAC 50/60Hz and single phase from 110–240VAC 50/60Hz, with no control transformer needed
- XT power controls: Eaton XT components with global ratings, compact size and a modular, plug-in design
- Four starting methods: auto, hand, remote start and pump start
- Programmable functions: two inputs, two output relays, five timers (minimum run, sequential start, pump run restart, acceleration and fail to start) and two virtual LEDs
- Alarm setpoints for phase reversal, phase failure, overvoltage and undervoltage
- History and diagnostics: 10,000 time-stamped messages, eight diagnostics and seven statistics; USB port to download message history and upload firmware
- Enclosures: NEMA 2 standard; NEMA 3R, 4, 4X and 12 available
- Standards: meets NFPA 20 and CE mark requirements, meets or exceeds UL 508, and is CSA approved
Ratings
| Line voltage | Motor horsepower |
|---|---|
| 200–208V, three phase | 1/3 – 20 HP |
| 220–240V, three phase | 1/3 – 20 HP |
| 380–415V, three phase | 1/3 – 40 HP |
| 440–480V, three phase | 1/3 – 50 HP |
| 550–600V, three phase | 1/3 – 50 HP |
| 120V, single phase | 1/3 – 2 HP |
| 240V, single phase | 1/3 – 5 HP |
XTJP part numbers explained
XTJP part numbers are built around the motor's full load amperage. For example, XTJP-G05-L1 is a three phase controller for motors drawing 4.1–6.3 A, with English labels in the standard NEMA 2 enclosure.
| Segment | Example | Meaning |
|---|---|---|
| Model | XTJP | JOCKEY Touch across-the-line jockey pump controller |
| Amperage range | G05 | Three phase: G01 0.6–1.0 A · G02 1.1–1.6 · G03 1.7–2.5 · G04 2.6–4.0 · G05 4.1–6.3 · G06 6.4–10.0 · G07 10.1–16.0 · G08 16.1–20.0 · G09 20.1–25.0 · G10 25.1–32.0 · G11 32.1–40.0 · G12 40.1–50.0 · G13 50.1–65.0 Single phase: G14 2.6–4.0 A · G15 4.1–6.3 · G16 6.4–10.0 · G17 10.1–16.0 · G18 16.1–20.0 · G19 20.1–25.0 · G20 25.1–32.0 · G21 32.1–40.0 · G22 40.1–50.0 · G23 50.1–65.0 |
| Horsepower and voltage (larger motors) | — | Larger units are specified by horsepower (15, 20, 25, 30, 40 or 50 HP) plus a voltage letter: A 208V/60Hz · B 240V/60Hz · C 380V/50Hz · D 480V/60Hz · E 600V/60Hz · F 415V/50Hz · H 380V/60Hz · J 400V/50Hz · K 400V/60Hz |
| Language | L1 | L1 English · L2 French · L5 Spanish · L6 Portuguese · L11 Turkish |
| Options | (none) | Added codes for enclosures and accessories (see below) |
XTJP options
| C1 / C2 / CX / FTS | Extra contacts: pump run / AC power failure / one form-C, specify function / fail to start |
| E1 / E2 / E3 | NEMA 3R / NEMA 4 / NEMA 12 enclosure |
| E5 / E9 / E10 | NEMA 4X: 304 stainless / painted steel / 316 stainless |
| E8 / EX | Tropicalization / export crating |
| POL / PRL / LX | "Power On" virtual LED / "Pump Run" virtual LED / custom virtual LED |
| P7 / P8 / P10 | Low suction pressure switch and alarm virtual LED / low suction shutdown (requires P7) / sea water rated pressure transducer |
| R1 / R2 / R3 | Space heater / with thermostat / with humidistat (externally powered) |
| USB | Externally mounted USB port |
XTJP controllers available to order online
| Part number | Supply | Motor full load amps |
|---|---|---|
| XTJP-G02-L1 | Three phase | 1.1–1.6 A |
| XTJP-G03-L1 | Three phase | 1.7–2.5 A |
| XTJP-G04-L1 | Three phase | 2.6–4.0 A |
| XTJP-G05-L1 | Three phase | 4.1–6.3 A |
| XTJP-G06-L1 | Three phase | 6.4–10.0 A |
| XTJP-G10-L1 | Three phase | 25.1–32.0 A |
| XTJP-G17-L1 | Single phase | 10.1–16.0 A |
| XTJP-G19-L1 | Single phase | 20.1–25.0 A |
Not sure which size you need? Send us the motor nameplate full load amps, voltage and phase and we'll match it.
What we need for a quote
- Jockey pump motor full load amps (from the motor nameplate) and horsepower
- Supply voltage and phase
- Enclosure type
- Options and label language
Have a full part number, a spec section or a photo of an existing nameplate? Send that instead and we'll match it. Call (786) 336-5783 or request a quote.
Bid submittals and documents
Three phase
- BR05805977K – 3 Phase, standard NEMA 2, options (PDF, eaton.com)
- BR05805877K – 3 Phase, Large HP, standard NEMA 2, options (PDF, eaton.com)
- BR05805777K – 3 Phase, NEMA 12, 3R, 4, 4X, options (PDF, eaton.com)
Single phase 120/240V
- BR05805677K – 1 Phase, standard NEMA 2, options (PDF, eaton.com)
- BR05805577K – 1 Phase, Large HP, standard NEMA 2, options (PDF, eaton.com)
- BR05805477K – 1 Phase, NEMA 12, 3R, 4, 4X, options (PDF, eaton.com)
Replacement parts
Keeping an existing jockey pump controller in service? Shop XTJP/XTJY components, JOCKEY Touch components, or browse all Eaton fire pump controller replacement parts.
Installation, wiring and commissioning should follow Eaton's instruction manual and NFPA 20 and be performed by qualified personnel.