Eaton FD90 Soft Start Fire Pump Controller (EPCT Fire)

This controller is quoted to your specifications. Call or Request a Quote Today.

The Eaton FD90 is the soft start model in Eaton's EPCT Fire line of electric fire pump controllers. It's a full-service, reduced-voltage controller that brings the motor up to speed with a smooth, step-less current ramp and slows it down just as smoothly, and it works with standard motors. Every FD90 is built to order, so we quote each one to your motor, voltage, enclosure and options. Call (786) 336-5783 or send us your catalog number or spec section.

How soft start works

The FD90 uses a solid-state starter that provides a step-less, smooth current ramp to the motor. This eliminates current surges and mechanical torque transients at start, which reduces stress on the motor, pump and piping. A soft-stop feature decelerates the motor smoothly as well, which helps reduce water hammer in the system. Other starting options include the FD30 across-the-line, FD40 part winding, FD60 autotransformer, and FD70 and FD80 wye-delta.

EPCT Fire features

  • 7" color touchscreen: 800x480 high-resolution display, a fast processor that reduces input lag, and a simplified tab system for navigation and programming
  • USB port: download history, statistics, configuration, diagnostics and start-up files; upload a configuration to reduce programming time; update firmware
  • Event history: logs up to 65,000 time-stamped events, with on-screen filtering for troubleshooting
  • Programmable output relays for common alarm, power/phase failure, phase reversal and pump run
  • Optional boards:
    • Relay board: four (4) one form-C programmable output relays
    • MODBUS board: output communication via RS422 or RS485
    • Secondary 4-20mA device board: additional connections for external pressure transducers, temperature sensors and similar devices
    • Alarm board: a supervisory powered alarm output
  • Enclosures: UL Type 2 (drip-proof) standard; Type 3, 3R, 4, 4X and 12 available
  • Standards: built to NFPA 20 and listed to UL 218. See the bid submittal for the full list of approvals.

FD90 catalog numbers explained

Every EPCT Fire catalog number follows the same pattern. For example, FD90-100-D-L2-E4 is a 100 HP, 480V/60Hz soft start controller with French labels in a NEMA 3 enclosure.

Segment Example Meaning
Model and starting type FD90 FD = stand-alone controller · 90 = soft start
Horsepower 100 Motor HP, from 5 to 700 HP. Not every HP is available at every voltage.
Voltage D A = 208V/60Hz · B = 240V/60Hz · C = 380V/50Hz · D = 480V/60Hz · E = 600V/60Hz · F = 415V/50Hz · H = 380V/60Hz · J = 400V/50Hz · K = 400V/60Hz
Language L2 L1 English · L2 French · L4 Italian · L5 Spanish · L6 Portuguese · L7 Chinese · L8 Polish · L9 Dutch · L11 Turkish
Options E4 Added codes for enclosures and accessories (see below)

Common options

E1 / E2 / E3 / E4 NEMA 3R / NEMA 4 / NEMA 12 / NEMA 3 enclosure
E5 / E9 / E10 NEMA 4X: 304 stainless / painted steel / 316 stainless
F2 Floor stand, 2 inch height (not available with NEMA 3, 4 or 4X)
H / I High or intermediate withstand rating
OP1 – OP4 Relay board, MODBUS board, secondary 4-20mA device card, alarm board
C1 – C5, CX Extra contacts (pump run, AC power failure, phase reversal, reservoir levels, custom)
P7 / P8 Low suction pressure switch / low suction shutdown
R1 – R7 Space heaters, with thermostat or humidistat options
B Alarm bell

See the full EPCT Fire option selection matrix for every code.

FD90 or FT90?

The FD90 is a stand-alone controller. If the fire pump also needs automatic transfer to an alternate power source, choose the FT90, which combines the soft start controller and a fire-pump-rated transfer switch in one assembly. You can also pair an FD90 with a separate FPATS stand-alone transfer switch.

What we need for a quote

  • Motor horsepower
  • Line voltage, phase and frequency
  • Enclosure type
  • Options and label language
  • Withstand rating, if your project requires high or intermediate

Have a full catalog number, a spec section or a photo of an existing nameplate? Send that instead and we'll match it. Call (786) 336-5783 or request a quote.

Bid submittal and documents

Replacement parts

Keeping an existing EPCT Fire controller in service? Shop EPCT Fire replacement components or browse all Eaton fire pump controller replacement parts.

Installation, wiring and commissioning should follow Eaton's instruction manual and NFPA 20 and be performed by qualified personnel.