Eaton FD60 Autotransformer Fire Pump Controller (EPCT Fire)
This controller is quoted to your specifications. Call or Request a Quote Today.
The Eaton FD60 is the autotransformer model in Eaton's EPCT Fire line of electric fire pump controllers. It's a full-service, reduced-voltage controller that cuts starting current while giving the motor a smooth acceleration, and it works with standard motors. Every FD60 is built to order, so we quote each one to your motor, voltage, enclosure and options. Call (786) 336-5783 or send us your catalog number or spec section.
How autotransformer starting works
The FD60 inserts an autotransformer in the power supply to the motor, reducing the voltage at the motor terminals for a smooth acceleration. After a short acceleration time, the main contactor bypasses the autotransformer and applies full voltage to the motor. Starting line current is 47% of the across-the-line starting inrush, approximately 280% of the motor's rated full load amperes. Other reduced-voltage options include the FD40 part winding (requires a part-winding motor), FD70 and FD80 wye-delta, and the FD90 soft start. Where full-voltage starting is acceptable, see the FD30 across-the-line controller.
EPCT Fire features
- 7" color touchscreen: 800x480 high-resolution display, a fast processor that reduces input lag, and a simplified tab system for navigation and programming
- USB port: download history, statistics, configuration, diagnostics and start-up files; upload a configuration to reduce programming time; update firmware
- Event history: logs up to 65,000 time-stamped events, with on-screen filtering for troubleshooting
- Programmable output relays for common alarm, power/phase failure, phase reversal and pump run
-
Optional boards:
- Relay board: four (4) one form-C programmable output relays
- MODBUS board: output communication via RS422 or RS485
- Secondary 4-20mA device board: additional connections for external pressure transducers, temperature sensors and similar devices
- Alarm board: a supervisory powered alarm output
- Enclosures: UL Type 2 (drip-proof) standard; Type 3, 3R, 4, 4X and 12 available
- Standards: built to NFPA 20 and listed to UL 218. See the bid submittal for the full list of approvals.
FD60 catalog numbers explained
Every EPCT Fire catalog number follows the same pattern. For example, FD60-150-D-L1 is a 150 HP, 480V/60Hz autotransformer controller with English labels in the standard enclosure.
| Segment | Example | Meaning |
|---|---|---|
| Model and starting type | FD60 | FD = stand-alone controller · 60 = autotransformer |
| Horsepower | 150 | Motor HP, from 5 to 700 HP. Not every HP is available at every voltage. |
| Voltage | D | A = 208V/60Hz · B = 240V/60Hz · C = 380V/50Hz · D = 480V/60Hz · E = 600V/60Hz · F = 415V/50Hz · H = 380V/60Hz · J = 400V/50Hz · K = 400V/60Hz |
| Language | L1 | L1 English · L2 French · L4 Italian · L5 Spanish · L6 Portuguese · L7 Chinese · L8 Polish · L9 Dutch · L11 Turkish |
| Options | (none) | Added codes for enclosures and accessories (see below) |
Common options
| E1 / E2 / E3 / E4 | NEMA 3R / NEMA 4 / NEMA 12 / NEMA 3 enclosure |
| E5 / E9 / E10 | NEMA 4X: 304 stainless / painted steel / 316 stainless |
| F2 | Floor stand, 2 inch height (not available with NEMA 3, 4 or 4X) |
| H / I | High or intermediate withstand rating |
| OP1 – OP4 | Relay board, MODBUS board, secondary 4-20mA device card, alarm board |
| C1 – C5, CX | Extra contacts (pump run, AC power failure, phase reversal, reservoir levels, custom) |
| P7 / P8 | Low suction pressure switch / low suction shutdown |
| R1 – R7 | Space heaters, with thermostat or humidistat options |
| B | Alarm bell |
See the full EPCT Fire option selection matrix for every code.
FD60 or FT60?
The FD60 is a stand-alone controller. If the fire pump also needs automatic transfer to an alternate power source, choose the FT60, which combines the autotransformer controller and a fire-pump-rated transfer switch in one assembly. You can also pair an FD60 with a separate FPATS stand-alone transfer switch.
What we need for a quote
- Motor horsepower
- Line voltage, phase and frequency
- Enclosure type
- Options and label language
- Withstand rating, if your project requires high or intermediate
Have a full catalog number, a spec section or a photo of an existing nameplate? Send that instead and we'll match it. Call (786) 336-5783 or request a quote.
Bid submittal and documents
Replacement parts
Keeping an existing EPCT Fire controller in service? Shop EPCT Fire replacement components or browse all Eaton fire pump controller replacement parts.
Installation, wiring and commissioning should follow Eaton's instruction manual and NFPA 20 and be performed by qualified personnel.