Every Eaton EPCT Fire electric fire pump controller has a catalog number that spells out exactly how it's built: the model, starting method, horsepower, voltage, label language and options. Use this page to decode a catalog number from a spec, a bid submittal or an existing nameplate, or to build one for a quote. Have a catalog number you'd like us to check? Call (786) 336-5783 or send it to us.
Catalog number format
[Model][Starting type] – [Horsepower] – [Voltage] – [Language] – [Options]
For example, FT90-60-D-L1-E5 is a soft start controller with automatic transfer switch (FT90), for a 60 HP motor (60) at 480V/60Hz (D), with English labels (L1), in a NEMA 4X 304 stainless steel enclosure (E5). More than one option code can be added to the end.
Model
| Code | Meaning |
|---|---|
| FD | Stand-alone fire pump controller |
| FT | Fire pump controller complete with automatic transfer switch |
| FDF / FTF | Foam pump versions of the FD and FT |
Starting type
| Code | Starting method | Stand-alone | With transfer switch |
|---|---|---|---|
| 20 | Limited service | FD20 | FT20 |
| 30 | Across-the-line | FD30 | FT30 |
| 40 | Part winding | FD40 | FT40 |
| 50 | Primary resistor | FD50 (call for availability) | FT50 (call for availability) |
| 60 | Autotransformer | FD60 | FT60 |
| 70 | Wye-delta (star-delta) open transition | FD70 | FT70 |
| 80 | Wye-delta (star-delta) closed transition | FD80 | FT80 |
| 90 | Soft start | FD90 | FT90 |
Horsepower
5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 350, 400, 450, 500, 550, 600, 650 and 700 HP. Higher horsepowers aren't available on all models, and limited-service controllers (20) are 30 HP maximum. Call for availability at your voltage.
Voltage
| Code | Voltage | Code | Voltage |
|---|---|---|---|
| A | 208V – 60Hz | F | 415V – 50Hz |
| B | 240V – 60Hz | H | 380V – 60Hz |
| C | 380V – 50Hz | J | 400V – 50Hz |
| D | 480V – 60Hz | K | 400V – 60Hz |
| E | 600V – 60Hz | G2 | 240V – 60Hz single phase (limited-service controllers only) |
Language
| Code | Language | Code | Language |
|---|---|---|---|
| L1 | English | L7 | Chinese |
| L2 | French | L8 | Polish |
| L4 | Italian | L9 | Dutch |
| L5 | Spanish | L11 | Turkish |
| L6 | Portuguese |
Options
| Code | Option |
|---|---|
| B | Alarm bell |
| C1 | Extra contacts "Pump Run" (one form-C) |
| C2 | Extra contacts "AC Power Failure" (one form-C) |
| C3 | Extra contacts "Phase Reversal" (one form-C) |
| C4 | Remote contacts, low reservoir (one form-C) |
| C5 | Remote contacts, high reservoir (one form-C) |
| CX | Extra contacts (one form-C; specify function) |
| E1 | NEMA 3R raintight enclosure |
| E2 | NEMA 4 watertight enclosure |
| E3 | NEMA 12 industrial dust-tight enclosure |
| E4 | NEMA 3 watertight enclosure |
| E5 | NEMA 4X 304 stainless steel enclosure |
| E8 | Tropicalization |
| E9 | NEMA 4X painted steel enclosure |
| E10 | NEMA 4X 316 stainless steel enclosure |
| EX | Export crating |
| F2 | Floor stand, 2 inch height * |
| H | High withstand rating |
| I | Intermediate withstand rating |
| OP1 | Optional relay board |
| OP2 | Optional MODBUS board |
| OP3 | Optional secondary 4-20mA device card |
| OP4 | Optional alarm board |
| P5 | Proof pressure switch, ALCO 15–290 PSI |
| P7 | Low suction pressure switch |
| P8 | Low suction shutdown (requires P7) |
| P10 | Pressure transducer, sea water rated |
| P13 | Externally mounted pressure transducer * |
| R1 | Space heater (120/220V) |
| R2 | Space heater with thermostat |
| R3 | Space heater with humidistat |
| R4 | Low pump room temperature switch ** |
| R5 | Space heater (internally powered, 120V) |
| R6 | Space heater with thermostat (internally powered, 120V/240V) |
| R7 | Space heater with humidistat (internally powered, 120V/240V) |
| TBE | Terminal block enclosure * |
* Not available with NEMA 3, 4 or 4X enclosures.
** When ordered with a NEMA 3, 4 or 4X enclosure, the temperature switch is shipped loose with 20 feet of wire.
Other Eaton catalog number formats
Some Eaton fire pump products use their own catalog number formats. Each is explained on its product page:
- FDM30 medium voltage controllers use medium voltage codes (2,200–6,900V)
- FD140 DPCT Fire diesel controllers use a model, language and options format
- FPATS stand-alone transfer switches
- Jockey pump controllers: XTJP, XTJY and XTJL
Source document
This page is based on Eaton publication PA124001EN, EPCT Fire option selection matrix. View the original PDF on eaton.com. Not every option is available in every combination; we'll confirm your configuration when we quote it.