Eaton FT60 Autotransformer Fire Pump Controller with Automatic Transfer Switch
This controller is quoted to your specifications. Call or Request a Quote Today.
The Eaton FT60 is the autotransformer model with automatic transfer switch in Eaton's EPCT Fire line of electric fire pump controllers. It combines a full-service, reduced-voltage autotransformer controller and a fire-pump-rated automatic transfer switch in one assembly, and it works with standard motors. Every FT60 is built to order, so we quote each one to your motor, voltage, enclosure and options. Call (786) 336-5783 or send us your catalog number or spec section.
How the FT60 works
The FT60 inserts an autotransformer in the power supply to the motor, reducing the voltage at the motor terminals for a smooth acceleration. After a short acceleration time, the main contactor bypasses the autotransformer and applies full voltage to the motor. Starting line current is 47% of the across-the-line starting inrush, approximately 280% of the motor's rated full load amperes. The integrated automatic transfer switch moves the fire pump to an alternate power source, such as a generator or second utility feed, when the normal source fails, and the EPCT Fire touchscreen manages both the controller and the transfer switch from one display.
FT60 controllers are supplied as dual utility controllers and meet FM 1321/1323 approvals. Other models with transfer switch include the FT30 across-the-line, FT40 part winding (requires a part-winding motor), FT70 and FT80 wye-delta, and the FT90 soft start.
EPCT Fire features
- 7" color touchscreen: 800x480 high-resolution display, a fast processor that reduces input lag, and a simplified tab system for navigation and programming
- USB port: download history, statistics, configuration, diagnostics and start-up files; upload a configuration to reduce programming time; update firmware
- Event history: logs up to 65,000 time-stamped events, with on-screen filtering for troubleshooting
- Programmable output relays for common alarm, power/phase failure, phase reversal and pump run
-
Optional boards:
- Relay board: four (4) one form-C programmable output relays
- MODBUS board: output communication via RS422 or RS485
- Secondary 4-20mA device board: additional connections for external pressure transducers, temperature sensors and similar devices
- Alarm board: a supervisory powered alarm output
- Enclosures: UL Type 2 (drip-proof) standard; Type 3, 3R, 4, 4X and 12 available
- Standards: built to NFPA 20, listed to UL 218, and FM 1321/1323 approved. See the bid submittal for the full list of approvals.
FT60 catalog numbers explained
Every EPCT Fire catalog number follows the same pattern. For example, FT60-150-A-L1 is a 150 HP, 208V/60Hz autotransformer controller with transfer switch and English labels in the standard enclosure.
| Segment | Example | Meaning |
|---|---|---|
| Model and starting type | FT60 | FT = controller with transfer switch · 60 = autotransformer |
| Horsepower | 150 | Motor HP, from 5 to 700 HP. Not every HP is available at every voltage. |
| Voltage | A | A = 208V/60Hz · B = 240V/60Hz · C = 380V/50Hz · D = 480V/60Hz · E = 600V/60Hz · F = 415V/50Hz · H = 380V/60Hz · J = 400V/50Hz · K = 400V/60Hz |
| Language | L1 | L1 English · L2 French · L4 Italian · L5 Spanish · L6 Portuguese · L7 Chinese · L8 Polish · L9 Dutch · L11 Turkish |
| Options | (none) | Added codes for enclosures and accessories (see below) |
Common options
| E1 / E2 / E3 / E4 | NEMA 3R / NEMA 4 / NEMA 12 / NEMA 3 enclosure |
| E5 / E9 / E10 | NEMA 4X: 304 stainless / painted steel / 316 stainless |
| F2 | Floor stand, 2 inch height (not available with NEMA 3, 4 or 4X) |
| H / I | High or intermediate withstand rating |
| OP1 – OP4 | Relay board, MODBUS board, secondary 4-20mA device card, alarm board |
| C1 – C5, CX | Extra contacts (pump run, AC power failure, phase reversal, reservoir levels, custom) |
| P7 / P8 | Low suction pressure switch / low suction shutdown |
| R1 – R7 | Space heaters, with thermostat or humidistat options |
| B | Alarm bell |
See the full EPCT Fire option selection matrix for every code.
FT60, FD60 or FD60 with FPATS?
If the fire pump doesn't need automatic transfer, the stand-alone FD60 autotransformer controller is the simpler option. Where the controller and transfer switch need to be separate, an FD60 can be paired with an FPATS stand-alone transfer switch.
What we need for a quote
- Motor horsepower
- Line voltage, phase and frequency
- Alternate power source (generator or second utility feed)
- Enclosure type
- Options and label language
- Withstand rating, if your project requires high or intermediate
Have a full catalog number, a spec section or a photo of an existing nameplate? Send that instead and we'll match it. Call (786) 336-5783 or request a quote.
Bid submittal and documents
Replacement parts
Keeping an existing EPCT Fire controller in service? Shop EPCT Fire replacement components, transfer switch components, or browse all Eaton fire pump controller replacement parts.
Installation, wiring and commissioning should follow Eaton's instruction manual and NFPA 20 and be performed by qualified personnel.